HGL type panel disconnect switch Suitable for AC 50HZ, rated voltage 400V/690V, rated current 125A, 160A. 3 poles & 4 poles. Different operating modes, can be divided indoor operation and outdoor operation. The contacts are made of copper and the cover is made of flame retardant plastic.
Modular Design
Optional micro switch
The terminal is Copper T3
3-poles or 4-poles
Avoid erroneous operations
Designed according to IEC/ EN 60974-3
Conventional current | 160A | ||||
Rated current In(A) | 125 | 160 | |||
Rated insulation voltage Ui (V) | 1000 | ||||
Dielectric strength (V) | 8000 | ||||
Rated working current | AC-21B | 125 | 160 | ||
380V | AC-22B | 125 | 160 | ||
AC-23B | 125 | 160 | |||
AC-21B | 125 | 160 | |||
660V | AC-22B | 125 | 160 | ||
AC-23B | 80 | 80 | |||
Motor power | 380V | 63 | 80 | ||
P (Kw) | 660V | 75 | 75 | ||
Rated short-time withstand current lcw (kA Rms) 0.1s/1s | 8 | 8 | |||
Rated breaking capability Icn (A Rms) AC23 380 V | 1000 | 1000 | |||
Rated making capability Icm (A Rms) AC23 380V | 1250 | 1600 | |||
Rated shortcurrent making capabilityIcm (kA peak value) | 13.6 | 13.6 | |||
Mechanical durability 380V | 1400 | 1400 | |||
Electical curability 380V | 200 | 200 | |||
Operation moment (Nm) | 6.5 | 6.5 | |||
Weight (kg) | 3 poles | 1.3 | 1.3 | ||
4 poles | 1.5 | 1.5 |
For general power transmission operation: firstly panel disconnect switch, and then close the circuit breaker or panel disconnect switch.
When the panel disconnect switch is powered off: first disconnect the circuit breaker or load switch, then disconnect the isolating switch.
When choosing, it is no different from other electrical equipment. It must be rated voltage, rated current, dynamic steady current, and thermal stable current.
The function of the panel disconnect switch is to disconnect the circuit without load current. The device to be repaired has obvious disconnection point from the power source to ensure the safety of the maintenance personnel. The panel disconnect switch has no special arc extinguishing device and cannot cut off the load current and short circuit current. Therefore, the panel disconnect switch must be operated only when the circuit is disconnected from the circuit breaker.